1. INTRODUCTION

1.1 About User Manual
This User Manual is designed to help you for quick installation of RG-T. Before installation and operation, please read this section very carefully.

1.2 Precautions for Safe Use and Installation
- Failure to follow those instructions will result in
death or serious injury.
- Disconnect all power before working on
equipment.
- When the device is connected to the network, do
not remove the back panel.
- Do not try to clean the device with solvent or the
like. Only clean the device with dried cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by
your component seller.
- Only for rack panel mounting.
- An F type fuse must be used and its current limit
value must be 6A.
- No responsibility is assured by ENTES A.S or any
of its subsidiaries for any consequences arising
out of the use of this material.

2. GENERAL

Power Factor Controllers are used for measurement and control of power factor control units for central reactive power compensation. The Power Factor measured by RG-T is compared with the set point values and in order to provide necessary compensation, Power Factor Controller switches capacitor banks ON and OFF automatically. RG-T is a microcontroller relay, designed for above application in 144x144 case for flush mounting with rear plug-in connectors.In addition to displaying the system‘s Cosφ in Automatic Operating Mode, RG-T displays the RMS values of Voltage(V) and Current (I), Active Power (W),Reactive Power (VAr) and Apparent Power (VA) of measuring phase.

3. FRONT PANEL SPECIFICATIONS

On the front panel of RG-T, there are warning lights, display and 3 buttons for settings.

3.1 Buttons and Lights
1. 1,2,.........,12: Shows the status of each capacitor steps.

2.SET Menu: Shows the Menu options that correspond to the lights.

3. AUTO/MAN Light: If this light is continuously ON, RG-T is in Automatic Mode. If it is blinking, RG-T is in Manual Mode. By pressing SET button 3 seconds,you enter to Menu and change operating Mode. (Refer to: 5.1)

4. Cosφ Light: By pressing SET button 3 seconds ; Cosφ Adjustment can be made by selecting this light. (Refer to: 5.3).
In Automatic Mode, when Cosφ light is selected by pressing UP nd DOWN buttons, system's Cosφ and ind/cap state is displayed.(Refer to: 5.10)

5.TIME/PF Light: By pressing SET button 3 seconds; you enter to Menu and Step Time adjustment is made by selecting this light. (Refer to: 5.4)
In Automatic Mode, when this light is selected by pressing UP and DOWN buttons, system's Power Factor is displayed. (Refer to: 5.11)

6.STEP/V Light: By pressing SET button 3 seconds; you enter to Menu and Step Number adjustment is made by selecting this light. (Refer to:5.5)
In Automatic Mode, when this light is selected by pressing UP and DOWN buttons phase voltage (V) is displayed. (Refer to:5.12)

7. PROGRAM/I Light: By pressing SET button 3 seconds; you enter to Menu and Power Sequence adjustment is made by selecting this light. (Refer to:5.6)
In Automatic Mode, when this light is selected by pressing UP and DOWN buttons phase current (I) is displayed (Refer to:5.12)

8.C/k - W Light: By pressing SET button 3 seconds; you enter to Menu and Manual C/k adjustment is made by selecting this light.(Refer to:5.7)
In Automatic Mode when this light is selected by pressing UP and DOWN buttons, system's Active Power (W) is displayed.(Refer to: 5.13)

9.CTR - VAr Light: By pressing SET button 3 seconds; you enter to Menu and Current Transformer Primary Value is made by selecting this light.(Refer to:5.8)
In Automatic Mode when this light is selected by pressing UP and DOWN buttons, system Reactive Power (VAr) is displayed.(Refer to: 5.14)

10.Over V. /VA Light: By pressing SET button 3 seconds; you enter to Menu and Protection of Capacitor Steps Against Over Voltage function is made by selecting this light. (Refer to:5.9)
In Automatic Mode when this light is selected by pressing UP and DOWN buttons, system Apparent Power (VA) is displayed.(Refer to: 5.15)

11.UP Button: To move up in the Menu.

12.SET Button: Enter button for different settings and values.

13.DOWN Button: To move down in the Menu.

14.Automatic C/k Setting: Automatical C/k adjustment is started by pressing UP and DOWN buttons together at the same time. (Refer to:5.2)

15. C+ Light: This light is ON when RG-T switches capacitor steps on.

16. NORMAL Light: This light is ON when the targeted compensation is achieved.

17.C- Light: This light is ON when RG-T switches capacitor steps off.

18.Insufficient Compensation Light: This warning light is ON when insufficient compensation occurs.(Refer to:6.1.2)

19.Over Compensation Light: This warning light is ON when over compensation occurs.(Refer to:6.1.3)

20.Over Voltage Light: This warning light is ON when over voltage occurs. (Refer to:6.1.1)

21.K (Kilo) Light: When this light is ON displayed value must be multiplied by 1000.

22.M (Mega) Light: When this light is ON displayed value must be multiplied by 10

4. CONNECTION DIAGRAM

Warnings:
a) Connection of a circuit breaker between the network and the power supply input of the device is highly recommended.
b) Circuit breaker must be in close proximity to the device.
c) Circuit breaker must be marked as the disconnecting device for the equipment.
d) All used fuses must be FF type and the current values of the fuses must be 2A, 3A and 6A.

5. CONTROLS AND MENU OPERATIONS

All settings are made by Menu.The set values except operating mode are kept in memory even if the device is switched off.When it is switched on, it starts compensation with the values stored in the memory in Automatic Operating Mode. After entering Menu by pressing SET button for 3 seconds and if you don make any adjustments during 20 seconds ,RG-T operates with the previously stored values.To quit Menu without any storing operation, UP or DOWN buttons are pressed until the ESC symbol is displayed and then SET button is pressed.The details of controls and adjustments are explained in the following sections.

5.1 Selection of Operating Mode(Automatic / Manual Mode )
Two Operating Modes are available for switching on/off the capacitor steps.
1) Automatic Operating Mode: The capacitor steps are controlled by RG-T, automatically.
2) Manual Operating Mode: The capacitor steps are switched on/off, manually.Mode selection is done as followed.

By pressing SET button 3 seconds SET Menu is started.

AUTO/MAN light is selected by using UP-DOWN buttons. (AUTO) symbol is displayed

AUTO/MAN setting is selected by pressing SET button. If the device is in Manual Mode, (A OF) symbol is displayed.If the device is in Automatic Mode, (A ON) symbol is displayed.

Automatic Mode (A OF)or Manual Mode (A ON) is selected by using UP-DOWN buttons.

When targeted operating mode is displayed, it is selected by pressing SET button. If Manual Mode is selected, AUTO/MAN light starts blinking and blinks during this mode.If Automatic Mode is selected, AUTO/MAN light is continuouslly ON during this mode.

5.1.1 Switching of the Capacitor Steps Manually

When RG-T is in Manual Mode, capacitor steps are connected by pressing UP button.Each time UP button is pressed, C+ light turns ON and one step is connected accordingly; NORMAL light will be ON after the connection of the step. This operation must be repeated to connect more steps.
Capacitor steps are disconnected by pressing DOWN button. Each time UP button is pressed, C- light turns ON and one step is disconnected after a delay time; NORMAL light will be ON after the disconnection of the step.This operation must be repeated to disconnect more steps.

5.2 Automatic C/k Adjustment
C/k adjustment is started by pressing UP-DOWN buttons together.

5.3 Cosφ Adjustment

When RG-T is in Manual Mode, capacitor steps are connected by pressing UP button.Each time UP button is pressed, C+ light turns ON and one step is connected accordingly; NORMAL light will be ON after the connection of the step. This operation must be repeated to connect more steps.
Capacitor steps are disconnected by pressing DOWN button. Each time UP button is pressed, C- light turns ON and one step is disconnected after a delay time; NORMAL light will be ON after the disconnection of the step.This operation must be repeated to disconnect more steps.

5.2 Automatic C/k Adjustment
C/k adjustment is started by pressing UP-DOWN buttons together.

5.3 Cosφ Adjustment

By pressing SET button 3 seconds, SET Menu is started

Cosφ light is selected by using UP and DOWN buttons. COS symbol is displayed

Cosφ adjustment is selected by pressing SET button. Previously adjusted value is shown at the display.

A value between 0.85-1.00 is adjusted by using UP-DOWN buttons.

When targeted value is displayed, it is strored by pressing SET button and RG-T returns to its normal operating mode.

5.4 Step Time Adjustment

By pressing SET button 3 seconds, SET Menu is started.

TIME light is selected by means of UP-DOWN buttons.

While TIME light is ON,(t 0n)symbol is displayed by means of UP-DOWN buttons and time delay adjustment for connection of capacitor steps to system is selected by pressing SET button.
While TIME light is ON, (t 0F)symbol is displayed by means of UP-DOWN buttons and time delay adjustment for disconnection of capacitor steps to system is selected by pressing SET button.

A value between 2-180sec. is adjusted by using UP-DOWN buttons.

When targeted value is displayed, it is stored by pressing SET button and RG-T returns to its normal operating mode.

5.5 Step Number Selection

By pressing SET button 3 seconds, SET Menu is started.

STEP light is selected by means of UP-DOWN buttons.(StEP) symbol is displayed.

STEP number adjustment is selected by pressing SET button.Previously selected value is shown on the display

A preferred step number is selected by means of UP-DOWN buttons.

When targeted value is displayed, it is stored by pressing SET button and RG-T returns to its normal operating mode.

5.6 Switching Program Selection

By pressing SET button 3 seconds, SET Menu is started.

PROGRAM light is selected by means of UP-DOWN buttons. (Prog) symbol is displayed.

Switching Program is selected by pressing SETbutton.Previously selected value is shown on the display

A value between PS1-PS5 is selected by using UP-DOWN buttons.

When targeted program is displayed, it is stored by pressing SET button and RG-T returns to its normal operating mode.

5.7 Selection of C/k Value by the User

By pressing SET button 3 seconds, SET Menu is started.

C/ k light is selected by means of UP-DOWN buttons. (CK) symbol is displayed.

Manual C/ k adjustment is selected by pressing SET button.Previously manually selected or automatically calculated C/ k value is shown on the display.

A value between 0.02-1 is selected by using UP-DOWN buttons.

When targeted value is displayed, it is stored by pressing SET button and RG-T returns to its normal operating mode.

5.8 Selection of Current Transformer Primary Value

By pressing SET button 3 seconds, SET Menu is started.

CTR light is selected by means of UP-DOWN buttons.(Ct) symbol is displayed.

Current Transformer Primary Value selected by pressing SET button. Previously selected CTR value is shown on the display.

A value between 5--10000 is adjusted by using UP-DOWN buttons.

5.9 Protection of Capacitor Steps Against Over Voltage

This is a selectable function, either O OF (Over Voltage Protection Off) or an Over Voltage value between 240-275V can be selected.If "Over Voltage" occurs when Over Voltage Value is selected (between 240-275V), then all the capacitor steps switch off, OVER VOLTAGE LED turns on and alarm relay activates. And if RG-T is on Manual Mode, it switches to Automatic Mode.
If 0 0F is selected; Then over voltage protection is disabled.Note: For over voltage values of RG-T with 380-415 VAC, please kindly check technical specifications.Setting can be made as followed.

Push SET button 3 seconds and enter SET

Scroll to "OVER V." by UP/DOWN buttons.(OV) is displayed.

Push SET button for Over Voltage Protection setting. Either(O OF) or preset over voltage value is displayed.

Select either (O OF) to cancel Over Voltage Protection Function or select a voltage value by UP/DOWN buttons.

Push SET button to store the selected value. RG-T returns to normal operating mode.

5.10 Display of Cosφ Value

When RG-T is in Manual Operating Mode, Cosφ value and inductive/capacitive state is always displayed. When Cosφ value is negative the system is capacitive and if Cosφ value is positive, the system is inductive.In Automatic Operating Mode, system's present Cos value and ind./cap. state may be displayed by selecting the Cosφ light, by means of UP-DOWN buttons.

5.11 Display of Power Factor (PF) Value
When RG-T is in Automatic Operating Mode (AUTO/MAN light is continuouslly ON), PF light is selected by means of UP-DOWN buttons and sytem's Power Factor value is displayed.This option is disabled in Manual Operating Mode.
Important Definition:Cosφ is defined as Displacement Power Factor and is relative to the fundamental harmonic only. PF is defined Total Power Factor and is relative to the all harmonics including fundamental harmonic. In a system without harmonics, PF and Cos are equal to each other.
Attention:The difference between cosφ and PF values does not mean that voltage harmonics, which leads to problems in systems, are high on the network.

5.12 Displaying RMS Values of Voltage and Current
When RG-T is in Automatic Operating Mode (AUTO/MAN light is ON) and V light is selected, RMS value of Voltage (V) is displayed.If I light is selected, RMS value of Current (I) is displayed. Displayed current and voltage values are of the phase where CT is connected. These options are disabled in Manual Operating Mode.

5.13 Display of Active Power (W) Value
When RG-T is in Automatic Operating Mode (AUTO/MAN light is continuouslly ON) and W light is selected by means of UP-DOWN buttons, system's Active Power value is displayed.
This option is disabled in Manual Operating Mode.

5.14 Display of Reactive Power (VAr) Value
When RG-T is in Automatic Operating Mode (AUTO/MAN light is continuouslly ON) and VAr light is selected by means of UP-DOWN buttons, system's Reactive Power value is displayed.
This option is disabled in Manual Operating Mode.

5.15 Display of Apparent Power (VA) Value
When RG-T is in Automatic Operating Mode (AUTO/MAN light is continuouslly ON) and VA light is selected by means of UP-DOWN buttons, system's Apparent Power value is displayed.
This option is disable in Manual Operating Mode.

6. DESCRIPTION

6.1 Errors and Warnings
The Alarm Relay is activated if the following "errors" occur.

6.1.1 Over Voltage
If the phase-neutral voltage of the L1 phase exceeds or equals to preset Over Voltage Value (between 240-275V), then RG-T waits for 3 seconds.At the end of 3 seconds if there is still over voltage, then OVER VOLTAGE LED turns on. Depending on selection of Over Voltage Protection Function(Pls. refer to 5.9), RG-T switches off all the capacitor steps or continues to compensation.
Over Voltage error disappears, if set Over Voltage value decreases by 4VAC.In this case, OVER VOLTAGE LED turns off and RG-T continues to compensation.

6.1.2 Insufficient Compensation
When target power factor is not reached although all the capacitor steps have been connected, INSUFFICIENT COMPENSATION light is ON and the Alarm Relay is activated.

6.1.3 Over Compensation
If the system is still capacitive although all the capacitor steps are disconnected, OVER COMPENSATION light is ON and Alarm Relay is activated.

6.2 Target Cosφ

The target Cosφ value can be adjusted between 0.85-1.00 inductive. RG-T connects capacitors in order to bring system's power factor to the adjusted value. The adjusted value is defined as 1.25xQ C1 value.Switching operation occurs out of this region.

6.3 Adjustable Step Switching Time

Step switching on/off delay time can be adjusted between 2 sec.-1800 sec.

Warning: Shorter time than above range can lead to damage in capacitors and conductors.
If capacitor banks do not have discharge coils, the delay time must be selected over 14 seconds. The selected delay time must not be shorter than the manufacturer's instruction.

6.4 Switching Program Selection
RG-T has 5 different program modes which determines the power ratio sequence of the capacitor steps:
PS1 selection ===> 1: 1: 1:.......: 1
PS2 selection ===> 1: 2: 2:.......: 2
PS3 selection ===> 1: 2: 4:.......: 4
PS4 selection ===> 1: 2: 4: 8:...: 8
PS5 selection ===> may be all of the above

6.4.1 RG-T Capacitor Sequence Examples
The power ratio selection between capacitor steps is very important. When choosing the ratio beetween the power of capacitor steps , the rating of each capacitor step value may exceed that of the first by a maximum amount equal to the total of the preceding capacitor steps value. So the first step value will be the smallest one and the following steps must be the multiplies of the first step.

Example: If the first capacitor power is 5 kVAr, the capacitor power sequence of the following
capacitors are as followed:
PS1 selection ===> 5. 5: 5:...............: 5
PS2 selection ===> 5: 10: 10:...........: 10
PS3 selection ===> 5: 10: 20:...........: 20
PS4 selection ===> 5: 10: 20: 40:.....: 40
PS5selection ===> may be all of the above

Two different switching programs exist in RG-T :
a)Rotational Switching: This switching program is rotational between equal steps in the clockwise direction. This ensures that the capacitor switching cycles are uniformly distributed over all steps and to provide minimum switching steps for maximum service life time of the system.There are 4 different rotational switching program options.(PS1,PS2,PS3,PS4)

b)Linear Operation: The switching program begins always from the first step to the last one in both switching on and off mode. The advantage of this switching program is the possibility of a large selection of capacitor steps conform to the step function ratio rule as explained above. The maximum possible ratio is "x:2x:4x:8x:16x...."
This switching program is selected by PS5 option.

6.5 Step Number Selection

By selecting the step number, the extra time is spent connecting on/off the unused capacitor steps is eliminated. As a result, compensation system is used more effectively and efficiently. If step number is not selected, RG-T makes the compensation according to the factory set step number which is max. available output as defined on the front panel.

6.6 C/k Setting
The C/k value is a threshold value for switching on/off the capacitor steps. C/k is the value obtained by dividing first step capacitor power "C" to the Current Transformer Ratio "k" This value is measured and calculated by RG-T automatically, or can be entered manually. After pressing the UP and DOWN buttons together, the C/k value is calculated and stored in one step switching on/off time interval. The further compensation controls are made with this stored value. In case of instantaneous change of the syste's load, measuring process will be renewed. RG-T will stop the measuring after 10 attempt.It means that the C/k value couldn't be measured due to the instability of the system's load. In this case, compensation control will continue with the previously stored value in the memory.

The formula to calculate the C/k value is :

Example :
Let the power (C) of the first step capacitor is 5 kVr and the Current Transformer Ratio(k) is 100/5.Then the C/k value is:

C/k = 5/(100/5)=0.25

C/k value for the different C and k values are as followed :

6.7 Sensing the Energy Flow Direction

RG-T has four quadrant measuring and operation feature. So it is able to sense the energy flow direction and to correct itself for right compensation

6.8 Current Transformer (CT) Selection
A separate CT must be always used for the Power Factor Controller. The wires connecting CT to Power Factor Controller must be as short as possible and the diameter of wire not less than 1.5 mm. Since the current information is supplied by CT, the right selection of CT is very important. The secondary current of the selected CT must comply with the following current limits for correct measuring.
Minimum=0.05 mA, Maximum=5.5 A (Minimum C/k Ratio must be 0.02)

7. ERROR DESCRIPTIONS

7.1 Wrong Cosφ

Current and Voltage phase connection are not correct.

7.2 Insufficient Compensation
The power value of the capacitor steps may be decreased by time.The fuses which are connected to the capacitors may be out of order. The power of the capacitor steps may be insufficient to compensate the system.(In this case, user must increase the capacitor power.)

7.3 Over Compensation
This occurs (especially at weekends, nights etc.) due to capacitive load current drawn by devices like ballasts, constant steps, etc. The contactor's contacts switching the capacitor steps may have stuck to each other due to the instantaneous over current.Unnecessary capacitor steps may have switched on manually.

7.4 Over Voltage
The phase-neutral voltage of L1 has exceeded the preset Over Voltage Value.

8. EASY INSTALLATION RECOMMENDATION (IMPORTANT NOTICE)

When the load is unstable and varies very quickly, the C/k calculation process may take long time or in some cases it can not be calculated properly or can be miscalculated which may cause improper compensation. A practical way to prevent this situation is as followed:

1- Turn on the compensation board without connecting the load current. Only the capacitors l be in operation in this situation (You can do this by switching off the load current temporarily).

2- Start the C/k calculation process by pressing the UP and DOWN buttons at the same time. Now , depending on the power of the first step, C/k value is calculated very accurately by RG-T. The calculated C/k value will automatically be stored in the memory. You can switch the load on. This C/k value will be kept in the memory until it is recalculated or changed manually.

9. TECHNICAL SPECIFICATIONS

Rated Voltage (Un)......:Please look at the back label.
Operating Voltage Range(DU).....: (0.9-1.1)xUn
Operating Current Range(DI).......: 50 mA-5.5A
Rated Frequency..............................: 50 Hz / 60 Hz
Measuring Class......................:1%±digit (V,I,cosφ),
2% ±digit(W,VAr,VA
Power Consumption................:Current: <2 VA
Voltage: 3 VA- 10 VA
Output Contact................:3 A ,750 VA (NO Contact)
No-Volt Feature.....:In case of power failure longer
than 200 msec.allcapacitor
steps are disconnected
automatically.
Setting Range.......:Manual C/k Setting:0.02-1.0
Cosφ Setting:0.85 (ind.)-1.00
CT Value:5-10000
CT Seconder 5A
Time Delay.............:Between 2 sec.-1800 sec.
Over Voltage Values..:240-275 V (Selectable)
(Un= 220, 230, 240 V AC )
410-480 V (Selectable)
(Un= 380, 400, 415 V AC )
105-140 V (Selectable)
(Un= 100, 110 V AC )
Factory Set Valu:Cosφ=1.00(ind.) ,Step Time=7 sn
Program=PS5 , C/k=0.05
CT Ratio =5
Number of Steps:RG12T(max 12) ; RG8T(max 8)
RG6T(max 6) ; RG5T(max 5)
Ambient Temperature:-5℃~55℃
Display................:4 Digit ,Red Display
Equipment Protection Class:Double Insulation-
Class ll
Wire Section (For Terminal Block):2.5 mm²
Terminal Block Protection Class:IP 00
Protection Class..........................:IP40
Connections...............:Socket terminals with screw
Switchboard cut-out...:139x139 mm
Weight.........................:0.8 kg.

Dimensions



  • Rated Current: 0.05-5.5A
  • Rated Voltage: 220V 50/60Hz
  • Origin: Mainland China
  • Certification: CE
  • Operating Current Range: 50mA-5.5A
  • CT. Value: 5A/5-10000A
  • Cos Seting: 0.85(ind.)-1.00
  • Over Voltage Values: 240-275VAC
  • Output Contact: 3A 750VAC (NO Contact)

VẬN CHUYỂN VÀ GIAO HÀNG

Chúng tôi tự hào cung cấp dịch vụ vận chuyển quốc tế hiện đang hoạt động tại hơn 200 quốc gia và hải đảo trên toàn thế giới. Không có gì có ý nghĩa hơn đối với chúng tôi ngoài việc mang lại cho khách hàng những giá trị và dịch vụ tuyệt vời. Chúng tôi sẽ tiếp tục phát triển để đáp ứng nhu cầu của tất cả khách hàng, mang đến một dịch vụ vượt ngoài mong đợi ở mọi nơi trên thế giới.

Bạn vận chuyển các gói hàng như thế nào?

Các gói hàng từ kho của chúng tôi ở Trung Quốc, Việt Nam sẽ được vận chuyển bằng ePacket hoặc EMS tùy thuộc vào trọng lượng và kích thước của sản phẩm. Các gói hàng được vận chuyển từ kho hàng tại Hoa Kỳ của chúng tôi được vận chuyển qua USPS.

Bạn có giao hàng trên toàn thế giới không?

Có. Chúng tôi cung cấp dịch vụ vận chuyển miễn phí đến hơn 200 quốc gia trên thế giới. Tuy nhiên, có một số địa điểm chúng tôi không thể vận chuyển đến. Nếu bạn sống ở một trong những quốc gia đó, chúng tôi sẽ liên hệ với bạn.

Còn về Hải Quan thì sao?

Chúng tôi không chịu trách nhiệm về bất kỳ khoản phí tùy chỉnh nào sau khi các mặt hàng đã được vận chuyển. Bằng cách mua sản phẩm của chúng tôi, bạn đồng ý rằng một hoặc nhiều gói hàng có thể được vận chuyển cho bạn và có thể nhận được phí tùy chỉnh khi chúng đến quốc gia của bạn.

Thời gian vận chuyển là bao lâu?

Thời gian vận chuyển khác nhau tùy theo địa điểm. Đây là những ước tính của chúng tôi:

Vị trí * Thời gian vận chuyển ước tính
Việt Nam, Châu Á 10-30 ngày làm việc
Hoa Kỳ 10-30 ngày làm việc
Canada, Châu Âu 15-35 ngày làm việc
Úc, New Zealand 10-30 ngày làm việc
Mexico, Trung Mỹ, Nam Mỹ 25-55 ngày làm việc
* Không bao gồm thời gian xử lý 2-5 ngày của chúng tôi.

Bạn có cung cấp thông tin theo dõi không?

Có, bạn sẽ nhận được email sau khi đơn đặt hàng của bạn được giao có chứa thông tin theo dõi của bạn.

Theo dõi của tôi cho biết "Hiện tại không có thông tin".

Đối với một số công ty vận chuyển, mất 2-5 ngày làm việc để thông tin theo dõi cập nhật trên hệ thống.

Các mặt hàng của tôi có được gửi trong một gói không?

Vì lý do hậu cần, các mặt hàng trong cùng một giao dịch mua đôi khi sẽ được gửi theo từng gói riêng biệt, ngay cả khi bạn đã chỉ định hình thức vận chuyển kết hợp.

Nếu bạn có bất kỳ câu hỏi nào khác, vui lòng liên hệ với chúng tôi và chúng tôi sẽ cố gắng hết sức để giúp bạn.

HOÀN TIỀN & CHÍNH SÁCH TRẢ LẠI

Hủy đơn đặt hàng

Tất cả các đơn đặt hàng có thể bị hủy cho đến khi chúng được chuyển đi. Nếu đơn đặt hàng của bạn đã được thanh toán và bạn cần thay đổi hoặc hủy đơn đặt hàng, bạn phải liên hệ với chúng tôi trong vòng 12 giờ. Sau khi quá trình đóng gói và vận chuyển đã bắt đầu, bạn không thể hủy quá trình này nữa.

Hoàn lại tiền

Sự hài lòng của bạn là ưu tiên số 1 của chúng tôi. Do đó, nếu bạn muốn được hoàn lại tiền, bạn có thể yêu cầu bất kỳ lý do nào.

Nếu bạn không nhận được sản phẩm trong thời gian đảm bảo (60 ngày không bao gồm quá trình xử lý 2-5 ngày), bạn có thể yêu cầu hoàn lại tiền hoặc đổi hàng.

Nếu bạn nhận được sai mặt hàng, bạn có thể yêu cầu hoàn lại tiền hoặc đổi hàng.

Nếu bạn không muốn sản phẩm mà bạn đã nhận, bạn có thể yêu cầu hoàn lại tiền nhưng bạn phải trả lại mặt hàng đó với chi phí của bạn và mặt hàng đó phải được sử dụng.

  • Đơn đặt hàng của bạn không đến được do các yếu tố trong tầm kiểm soát của bạn (tức là cung cấp địa chỉ giao hàng sai)
  • Đơn đặt hàng của bạn đã không đến do những trường hợp ngoại lệ nằm ngoài tầm kiểm soát của Shoplatvat (ví dụ: chưa được hải quan thông quan, chậm trễ do thiên tai ...).
  • Các trường hợp ngoại lệ khác ngoài tầm kiểm soát của shoplatvat.com

* Bạn có thể gửi yêu cầu hoàn lại tiền trong vòng 15 ngày sau khi thời hạn giao hàng được đảm bảo (90 ngày) đã hết. Bạn có thể làm điều đó bằng cách gửi tin nhắn tại Trang Liên Hệ

Nếu bạn được chấp thuận cho khoản tiền hoàn lại, thì khoản tiền hoàn lại của bạn sẽ được xử lý và một khoản tín dụng sẽ tự động được áp dụng cho thẻ tín dụng hoặc phương thức thanh toán ban đầu của bạn, trong vòng 14 ngày.

Đổi Trả Hàng

Nếu vì bất kỳ lý do gì bạn muốn đổi sản phẩm của mình, có thể lấy một cỡ quần áo khác. Bạn phải liên hệ với chúng tôi trước và chúng tôi sẽ hướng dẫn bạn thực hiện các bước.

Vui lòng không gửi lại giao dịch mua của bạn cho chúng tôi trừ khi chúng tôi cho phép bạn làm như vậy.

DỊCH VỤ ĐƠN HÀNG LỚN

Wholesale

Cảm ơn bạn đã quan tâm đến kinh doanh với chúng tôi!

Nếu bạn muốn nhận được mức giá chiết khấu cho các đơn đặt hàng lớn của mình, hãy điền vào các ô trống bắt buộc cùng với địa chỉ email của bạn, ID mặt hàng sản phẩm # và / hoặc liên kết của mặt hàng bạn muốn đặt, số lượng mặt hàng (tối thiểu là 30 cái), quốc gia vận chuyển và phương thức thanh toán là bắt buộc. Chúng tôi sẽ liên hệ với bạn với mức giá ưu đãi ngay khi nhận được yêu cầu của bạn.

Cùng một người bán